Example
// Server Side Connections 
Connections 
Port,  Protocol,  Baud,  Parity,  Handshaking, 
P1,  TIWAY_BDLC,  9600,  None,  None, 
5.2.  Server Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
Secondary PLC station address 
of physical server node 
1-254 
Protocol  Specify protocol used  TIWAY, TIWAY_BDLC 
Server_Hold_Timeout* 
Specifies time FieldServer will 
reserve server side connection 
while waiting for the Client side 
to update data in Data_Array (if 
necessary) 
>1.0s 
Example
// Server Side Nodes 
Nodes       
Node_Name,  Node_ID,  Protocol   
PLC_01,  01,  TIWAY_BDLC   