C40_REP_NM_CONFIG, Nm_Config,  0,  RDBC, PLC_01,  Report_NM_Config,  16, 
Scan_Interval 
0s 
The above map descriptor will continuously execute the indicated host adapter command and will store the 
following parameter values in the data array “Nm_Config”: 
Offset Parameter 
0  Dipswitch 1 and 2 settings 
1  Config flag ( 0 = Network Manager not configured, 1 = Network Manager configured ) 
2  Option 01 configuration value 
3  Option 02 configuration value 
4  Option 03 configuration value 
5  Option 04 configuration value 
6  Option 05 configuration value 
7  Option 06 configuration value 
8  Option 07 configuration value 
9  Option 08 configuration value 
10  Option 09 configuration value 
11  Option 0A configuration value 
12  Option 0B configuration value 
13  Option 0C configuration value 
14  Option 0D configuration value 
15  Option 0E configuration value 
4.4.6.5. Soft Reset 
Forces the UNILINK Host Adapter to do a software reset. 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Host_Adapter_Cmd, Length 
C41_SOFT_RESET, Cmd_Triggers, 0, AWT, PLC_01, Soft_Reset, 1 
The above map descriptor will execute the indicated host adapter command once every time a value is written to 
the data array “Cmd_Triggers” at offset 0. 