User Guide
FS-8700-31 Siemens TIWAY I  Page 11 of 23 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
The above map descriptor will continuously write data of type “Loop_Gain” to 2 PLC data memory addresses of 5 
and 9. The data to write will be collected from the data array “FLOAT_Data” from offsets 0 and 1. 
4.4.5.3.  Writing the same value to a block of contiguous PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
C18_FLOAT_PLC254, FLOAT_Data,  10,  WRBC, PLC_254,  Loop_Reset,  0,  3, 
TIWAY_Fill_Block_Value, Scan_Interval 
50.5, 0s 
The above map descriptor will continuously write a value of 50.5 of type “Loop_Reset” to 3 contiguous PLC data 
memory addresses starting from 0. 
4.4.5.4.  Writing Drum_Count_Preset data to contiguous PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
C08_RAW16_PLC01, RAW16_Data,  70,  WRBC, PLC_01,  Drum_Count_Preset, 0,  5, 
Preset_Step_List, Scan_Interval 
5 8 9 33 49,  0s 
The above map descriptor will continuously write data of type “Drum_Count_Preset” to 5 PLC data memory 
addresses. The data to write will be collected from the data array “RAW16_Data” from an offset of 70. The Preset 
Steps associated with the addresses are (address 0):5, (address 1):8, (address 2):9, (address 3):33, and (address 
4):49. 
4.4.5.5.  Writing Drum_Count_Preset data to random PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, TIWAY_Address_List, 
C08_RAW16_PLC01, RAW16_Data,  70,  WRBC, PLC_01,  Drum_Count_Preset, 5 9, 
Length, Preset_Step_List, Scan_Interval 