4.4.4.  Reading TIWAY data map descriptor examples 
4.4.4.1.  Reading data from contiguous PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
C01_RAW16_PLC01, RAW16_Data,  0, RDBC, PLC_01, IE_Ladder, 0, 10, 
Scan_Interval 
0s 
The above map descriptor will continuously read 10 data elements starting from address 0 of type “IE_Ladder” from 
PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 0. 
4.4.4.2.  Reading data from random PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type,  TIWAY_Address_List, Length, 
C02_RAW16_PLC01, RAW16_Data,  10,  RDBC,  PLC_01,  Variable,  5 9,  2, 
Scan_Interval 
0s 
The above map descriptor will continuously read 2 data elements from address 5 and 9 of type “Variable” from 
PLC_01. The data will be stored in the data array called “RAW16_Data” from an offset of 10. The data will be 
stored at offsets 10 and 11.  
4.4.4.3.  Reading Drum_Count_Preset data from contiguous PLC data memory locations 
Map_Descriptor_Name, Data_Array_Name, Data_Array_Offset, Function, Node_name, TIWAY_Data_Type, Address, Length, 
C08_RAW16_PLC01, RAW16_Data,  70,  RDBC, PLC_01,  Drum_Count_Preset, 0,  5, 