4.3.2.  Driver Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name 
Name of Node to 
communicate with 
One of the node names 
specified in “Node Descriptor” 
above 
Block_Number  PLC File Number 
For local node 7-39 
For remote node 1-999 
PCCC_Type 
Type of PCCC data to be 
transferred over 
ControlNet 
UINT, (SINT, INT) (REAL, 
FLOAT) (BOOL, BIT, FLAG) 
Equal types are shown in 
brackets. 
Address  Starting address within file 
0 – 999 ( INT, SINT ) 
0 – 499 ( REAL, FLOAT ) 
0 – 15999 ( BOOL, BIT, FLAG )
Length  Length of Map Descriptor 
1 – 249 ( INT, SINT ) 
1 – 124 ( REAL, FLOAT ) 
1 – 3984 ( BOOL, BIT, FLAG ) 
Note the number of bytes per PCCC_Type: 
SINT, INT = 2 bytes, REAL, FLOAT = 4 bytes, BOOL, BIT, FLAG = 8 bits per byte 
Each PLC file is 2000 bytes long and therefore the address values will range from zero 
to a maximum value as indicated. The start address is specified in increments of the 
basic data type specified under PCCC_Type. 
The message buffers in the ControlNet card are each 498 bytes long and only one 
message buffer can be allocated to a Map Descriptor. The Map Descriptor lengths are 
therefore limited to maximum values as indicated when taking the data type byte lengths 
into account. 
4.3.3. Timing Parameters 
Column Title  Function  Legal Values 
Scan_Interval  Rate at which data is polled  >0.1s 