User Guide
FS-8700-24 ControlNet Driver Manual    Page 8 of 12 
4.2.   ControlNet Node Descriptors 
This section of the configuration file defines the different MacIds of the ControlNet devices 
on the network. If you want to transfer the data on the local ControlNet card to the data-
arrays on your FieldServer, typically used when acting as a Server, define a Node_ID with 
the same value as the System_Station_Address. 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
ControlNet MacId of the node 
to communicate with 
1-99 
Protocol  Specify protocol used  ControlNet 
Example 
// ControlNet Nodes     
Nodes     
Node_Name,  Node_ID,  Protocol 
PLC_1,  1,  ControlNet 
Local,  5,  ControlNet 
4.3.  Unscheduled Map Descriptors using PCCC messaging 
Maintained on the SST 5136-CN-ISA card are 32 integer files (N7-N39) that can be read or 
written to by other devices on the ControlNet network using PCCC messaging. Client style 
Map Descriptors are used to transfer data to or from the file buffers on the card to the Data 
Arrays on the FieldServer. 
4.3.1. FieldServer Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name 
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name  Name of Data Array 
One of the Data Array 
names from “Data Array” 
section above 
Data_Array_Offset  Starting offset in Data Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
RDBC, WRBC, WRBX 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldServer.com 