4.  Configuring the FieldServer as a ChB-Link Client 
For  a  detailed  discussion  on  FieldServer  configuration,  please  refer  to  the  FieldServer 
Configuration Manual.  The information that follows describes how to expand upon the factory 
defaults provided in the configuration files included with the FieldServer (See ā.csvā sample files 
provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer 
to communicate with a ChB-Link Server 
Note that * indicates an optional parameter, with the bold legal value being the default. 
4.1.  FieldServer 
Section Title 
Bridge 
Column Title  Function  Legal Values 
Title  Title for CSV file  Any text, Maximum 32 characters 
System_Node_ID  Node ID of the FieldServer  8 ā 254 
Example 
// Common Information 
Bridge   
Title,  System_Node_ID 
CB_Link client,  11 
4.2.  Data Arrays/Descriptors 
Section Title 
Data_Arrays 
Column Title  Function  Legal Values 
Data_Array_Name  Provide name for Data Array  Up to 15 alphanumeric characters 
Data_Format  Provides data format  INT16, INT32, BIT, FLOAT 
Data_Array_Length  Number of Data Objects  1-10,000 
Example 
// Data Arrays 
Data_Arrays     
Data_Array_Name,  Data_Format,  Data_Array_Length 
DA_AI_01,   Float,   200 