4.2  Neuron ID 
The  driver  prints  the  Neuron  ID  on  the  Driver  Message  Screen  as  its  starts. On  FS-B2011  and  FS-B4011  FieldServers  it  is 
possible to print the Neuron ID on the Error Screen at any time by pushing the Service Button on the side of the FieldServer. 
On all platforms, the driver can store the Neuron ID in a Data Array so that it can be read by a Client node – Refer also to 
Appendix C.3. 
4.3  Lon LED’s 
The location of the Lon LED varies between FieldServer’s.  Please consult the Start-up guide for the FieldServer in question. 
Lon LED is consistent with the table below for all FieldServers. 
Explicit 
Implicit – Not Commissioned 
Implicit – Commissioned 
Off 
Flashing 
Off 
4.4  The LonWorks Adapter Card (FS-X40 only) 
4.4.1  Port Address Switch 
The LonWorks driver has been configured to access the LonWorks card at ISA port address 340 hex. This is the default setting 
for the card, and the DIP switches must not be modified. The DIP switch setting on the card is as follows: 
Switch 
Setting 
1 
ON 
2 
ON 
3 
OFF 
4 
ON 
5 
OFF 
6 
OFF 
7 
OFF 
8 
OFF 
Lon LED 