User Guide
FS-8700-21 LonWorks Manual                Page 53 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
SNVT_pumpset_mn 
Data Length 
8 
Suggested Data Array Formats 
Byte, Uint16, Float 
Data Item 1 
pset_main_pump 
Measurement 
Units 
Values Range 
Invalid Value 
motor_state_t 
N/A 
0 .. 7 
255 (0xFF)(MOTOR_NUL) 
Data Item 2 
pset_booster_pump 
Measurement 
Units 
Values Range 
Invalid Value 
motor_state_t 
N/A 
0 .. 7 
255 (0xFF)(MOTOR_NUL) 
Data Item 3 
pset_prio_level 
Measurement 
Units 
Values Range 
Invalid Value 
priority_level_t 
N/A 
0 .. 11 
255 (0xFF)(PR_NUL) 
Data Item 4 
pset_process_ready 
Measurement 
Units 
Values Range 
Invalid Value 
Boolean_t 
Bit 
0, 1 
255 (0xFF)(BOOL_NUL) 
Data Item 5 
pset_emerg_stop 
Measurement 
Units 
Values Range 
Invalid Value 
Boolean_t 
Bit 
0, 1 
255 (0xFF)(BOOL_NUL) 
Data Item 6 
pset_main_pumpd_ena 
Measurement 
Units 
Values Range 
Invalid Value 
Boolean_t 
Bit 
0, 1 
255 (0xFF)(BOOL_NUL) 
Data Item 7 
pset_boost_pumpd_ena 
Measurement 
Units 
Values Range 
Invalid Value 
Boolean_t 
Bit 
0, 1 
255 (0xFF)(BOOL_NUL) 
Data Item 8 
pset_maint_req 
Measurement 
Units 
Values Range 
Invalid Value 
Boolean_t 
Bit 
0, 1 
255 (0xFF)(BOOL_NUL) 