Appendix B.2. Neuron Systems 
Newron Systems may produce the following Error message “bindings lost after power-cycle” The solution to this is 
to place the FieldServer in the Configured state which will cause the bindings to be committed to the Neuron and 
they will remain after a power cycle. 
Procedure: 
1) Make the bindings in NL220 
2) Place devices in ONLINE mode or state. 
3) Refer to the following Screencap for assistance in placing the FieldServer in the Configured state.  
Appendix B.3. Honeywell Care 
This  system  uses  unacknowledged  service  as  default.  This protocol  driver  requires acknowledged  service  to 
operate correctly. 
Appendix B.4. Tridium JACE 
This  system  uses  unacknowledged  service  as  default.  This protocol  driver  requires acknowledged  service  to 
operate correctly. 
Note that Tridium calls Acknowledged service “critical bindings”. 