Appendix B. Vendor Information 
Appendix B.1. Echelon LonMaker 
Appendix B.1.1.  Using LonMaker to commission the FieldServer  
  Ensure  that  the correct  firmware and  latest  configuration  is  loaded  on the  FieldServer  (Each  change in  the 
FieldServer requires re-commissioning of the FieldServer in LonMaker) 
  Ensure that the FieldServer and the LonMaker machine are on the same network. 
  Open the existing Network in LonMaker, or create a new Network 
  Click on “Create New Network” and follow the network wizard, making the following selections: 
  Network Interface: Choose Network Attached 
  Management Mode: Choose Onnet unless you are working offline 
  Register Plug-ins required. None 
  Once Visio is open with the Network showing, drag a new device onto the drawing from the toolbox. 
  Follow the Device Network, making the following selections 
  Enter Device Name: Choose commission device 
  Specify Device Template: Choose upload from device 
  Specify Device Channel: Choose Auto Detect 
  Specify Device Properties: Leave as is (Ping is optional) 
  Identify Device: Choose service pin 
  Device Application Image: Leave unchecked 
  Initial State: Leave as is 
  Press the service pin on the FieldServer when asked to do so, and the FieldServer will be commissioned. 
  Drag a new function block onto the drawing from the toolbox. Give the function block a name and ensure that 
it is allocated to the FieldServer device. 
  Once the function block is on the drawing, drag input and output variables onto the function block.  LonMaker 
will display the variables available for binding. Click on the variables you require (or use the select all option), 
and they will be commissioned onto the function block. 
  Connect these  variables to  other devices by dragging connections from the toolbox and  connecting the 
variables. 
Appendix B.1.2.  Removing Previous FieldServer Device Templates in LonMaker.  
If  you  have  previously  used  LonMaker  to  commission  a  FieldServer  or  ProtoCessor  onto  a  LonWorks  network, 
LonMaker saves the properties of that device as a device template.  It is important to remove all previous device 
templates from LonMaker when moving onto your next FieldServer product as some parameters might transfer to 
your new device. 
To remove the device templates, open your  LonMaker  workspace as you would  normally  do.    Then choose the 
LonMaker toolbar  and  choose  the  Device  Templates option.   This  will  bring up  a  list  of  all device  templates. 
Highlight and then remove all device templates that do not contain “Echelon” or “LNS”.  This will ensure a fresh 
commission of your FieldServer product. 