User Guide
FS-8700-21 LonWorks Manual                Page 19 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
6.2.5  Map Descriptor Example 1 - Explicit Configuration using Network Management Polls 
The Map Descriptor pollTemp_p shows the use of SNVT_Units for Scaling when polling temperature 
The Map Descriptor pollSwitch shows the use of SNVT_Option for Selective data scanning. This only brings in the “State” portion of SNVT_Switch 
Map_Descriptors 
Map_Descriptor_Name 
,Data_Array_Name 
,Data_Array_Offset 
,Lon_Function 
,Function 
,Node_Name 
,SNVT_Index  
,SNVT_Type 
,SNVT_Units 
,SNVT_Option 
,Scan_Interval 
pollTemp_p  
,DA_Explicit 
,1 
,NMFETCHC  
,Rdbc 
,Remote_Node 
,0 
,SNVT_temp_p  
,Deg_F 
,-  
,1.0s 
pollSwitch 
,DA_Explicit 
,2 
,NMFETCHC  
,Rdbc 
,Remote_Node 
,1 
,SNVT_switch  
,-  
,State 
,1.0s 
6.2.6  Map Descriptor Example 2 – Polling UNVT’s 
Map_Descriptors 
Map_Descriptor_Name 
,Data_Array_Name 
,Data_Array_Offset 
,Lon_Function 
,Function 
,Node_Name 
,SNVT_Index  
,SNVT_Type 
,UNVT_Byte_Length 
,Scan_Interval 
pollUNVT  
,DA_Explicit 
,101 
,NMFETCHC  
,Rdbc 
,Remote_Node  
,2 
,UNVT 
,31 
,1.0s 
Explicitly Addressed Client Map Descriptors use 
this field to point to their relevant Server Map 
Descriptors. 
For Non-Throttled 
Client Map 
Descriptors the 
Scan_Interval 
determines the 
update rate. 
This field 
determines the 
Map 
Descriptor’s 
function. See 
Section 6.1.2 
for more 
information. 
UNVT Byte length must be specified for correct 
operation. 