User Guide
FS-8700-21 LonWorks Manual                Page 18 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
6.2.3  Driver Related Map Descriptor Parameters 
Column Title 
Function 
Legal Values 
Node_Name 
Name of Node to fetch data from or send data to. Needed for Explicit 
Addressing. 
One  of  the  node  names 
specified in  “Client  Node 
Descriptors” above 
SNVT_Index 
Server Network Variable Index 
0-4095 
SNVT_Type 
Standard network variable type of the data  
See Appendix D 
SNVT_Option* 
Specifies which record out of a complex SNVT we are after.  
See Appendix A.9.1 
SNVT_Units* 
Specifies  the  measurement  units  if  something  other than  Metric  is 
required 
See Appendix A.9.2 
UNVT_Byte_Length* 
Specifies the length in bytes of an UNVT. This Parameter is compulsory 
when  SNVT_Type  is  set  to  UNVT,  the  parameter  is  not  used  on 
conjunction with SNVT’s 
1-255. See Appendix A.1 
UNVT_ID 
Specifies  the  Type  Number  to  apply  to  this  particular  UNVT.  This 
Parameter is optional when SNVT_Type is set to UNVT, The parameter 
is not used on conjunction with SNVT’s 
0, 146-255.  See Appendix 
A.1. 
NV_Min_Value* 
Network  Variable updates  with  values  less than  specified  in  this  field 
will be ignored. 
See Appendix A.2  
NV_Max_Value* 
Network Variable updates with values higher than specified in this field 
will be ignored. 
See Appendix A.2  
NV_Delta_Value* 
Network Variable updates where the value’s delta change is less than 
specified  in  this  field  will  be  ignored  unless  the  Max_Scan_Time 
Condition has been met. Compulsory for Throttling Lon Functions only. 
Not used on other Lon Functions. 
See Appendix A.2  
NV_Selfdoc_Text* 
The Self-Documenting String for this Network Variable. 
Normal  Text  up  to  a 
length of 40 characters 
6.2.4  Timing Parameters 
Column Title 
Function 
Legal Values 
Scan_Interval* 
Seconds per scan 
0-32000,  
2s 
Min_Scan_Time* 
Minimum Scan  Time in  seconds.  Compulsory  for  Throttling Lon Functions only.  Not 
used on other Lon Functions. 
See  Appendix 
A.3 
Max_Scan_Time* 
Maximum Scan  Time in seconds. Compulsory for  Throttling Lon Functions only. Not 
used on other Lon Functions. 
See  Appendix 
A.3 