User Guide
FS-8700-21 LonWorks Manual                Page 10 of 62 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
5.1.5  Network Management Capability 
When  commissioning  an  implicitly  configured  FieldServer  using  the  "Traditional"  binding  method,  the  configuration 
parameters below are all that is needed to achieve this purpose.   For hints and tips on how to commission the FieldServer 
using the various Vendor devices that do this, see Appendix B 
It is possible to set the FieldServer Online and Offline using the Network Management Tools. This is a LonWorks function, and 
is  different  from  the  traditional  Online  and  Offline  Status  discussed  in  other  FieldServer  documentation.    When  the 
FieldServer is set offline using this LonWorks feature it will not communicate with other LonWorks devices. 
5.1.6  Client vs Server Mapping 
Distinguishing Client from Server in the LonWorks Environment is more difficult due to the "Peer to Peer" nature of LonWorks 
design. Clients and Servers can be identified in this environment as follows: 
  Clients will write Setpoints and have status written to them, so expect Setpoints and Control Points on the Output side, 
and Status and Alarms on the Input side 
  Servers will have the opposite structure, with Setpoints and Control Points on the Input Side and Staus and Alarms on the 
Output side 
Distinguishing Client from Server is important to ensure correct matching with other protocols being used on a FieldServer. 
For example, it would not be useful to map an Output to a BACnet AI point as both points will be expecting to push data out 
of the FieldServer. 
5.2  Client Side Mapping 
5.2.1  Connection Parameters 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Protocol 
Specify protocol used 
LonWorks 
Connection_Type* 
Specify Network Management.  Primarily used for Circon_SI, refer 
to Appendix C.5. 
LonMaker,  LonWatcher, 
Circon_SI, None 
Example 
// Client Side Connections 
Connections 
Adapter 
,Protocol 
LonWorks 
,LonWorks 










