4.3.  Client Side Connection Descriptions 
The adapter used for the Profibus driver must be declared in the connections section. 
Section Title 
Connections 
Column Title  Function  Legal Values 
Adapter Adapter Name  Prof_DP 
Protocol  Specify protocol used  Profibus_DP 
Example
// Client Side Connections 
Connections 
Adapter,  Protocol 
Prof_DP,  Profibus_DP 
4.4.  Client Side Node Descriptors 
For each Profibus slave that the user wishes to access data on, an entry into a node table 
must be made. The table associates a name with the node number and connection. 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node 
Up to 32 alphanumeric 
characters 
Node_ID 
Station ID of destination Profibus 
device 
0-125 ( do not use same ID as in 
System_Station_Address) 
Protocol  Specify protocol used  Profibus_DP 
Adapter 
Specify which adapter is 
connected to the FieldServer 
Prof_DP 
Example
// Client Side Nodes 
Nodes       
Node_Name,  Node_ID,  Protocol,  Adapter 
PDP_01,  1,  Profibus_DP,  Prof_DP 