4) Set the Baud Rate to a value supported by the Slaves and your cabling media. Choose a 
highest Station on the network if you wish to enhance performance, which will prevent the 
Master from scanning non-existant Stations. Click OK to complete the network configuration. 
5) Drag your Slave devices onto the right window pane and configure them as per 
manufacturer’s instructions. Choose a unique Station ID for each Slave. 
There has to be Node descriptor with matching Node ID to Station ID for each Slave setup 
in the FieldServer’s config.csv file. 
Important Note: 
All Profibus Masters check for a match in the connection size in bytes to Slaves before 
allowing a connection. Make sure you add the appropriate Modules for Input/Output Data to 
create a connection size that matches the connection size setup in the Slave device; 
otherwise the Master will not connect to the Slave. 