Technologies Computer Driver Instruction Manual
FS-8700-16 BACnet PTP Serial Driver Manual        Page 8 of 20 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970  email: support@fieldserver.com 
4.5.4.  Map Descriptor Example 
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  Data_Type,  Object_Instance  Property,  Scan_Interval 
CMD_AI_01,  DA_AI_01,  0,  RDBC,  BCU_1,  AI,  1,  Present_Value,  20.000s 
CMD_AI_02,  DA_AI_01,  1,  RDBC,  BCU_1,  AI,  2,  Present_Value,  20.000s 
CMD_AI_03,  DA_AI_01,  2,  RDBC,  BCU_1,  AI,  3,  Present_Value,  20.000s 
CMD_AO_01,  DA_AO_01,  0,  RDBC,  BCU_1,  AO,  1,  Present_Value,  30.000s 
CMD_AO_02,  DA_AO_01,  1,  RDBC,  BCU_1,  AO,  2,  Present_Value,  30.000s 
CMD_AO_03,  DA_AO_01,  2,  RDBC,  BCU_1,  AO,  3,  Present_Value,  30.000s 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  Data_Type,  Object_Instance,  Property,  Scan_Interval 
CMD_DI_01,  DA_DI_01,  0,  RDBC,  BCU_1,  DI,  1,  Present_Value,  15.000s 
CMD_DI_02,  DA_DI_01,  1,  RDBC,  BCU_1,  DI,  2,  Present_Value,  15.000s 
CMD_DI_03,  DA_DI_01,  2,  RDBC,  BCU_1,  DI,  3,  Present_Value,  15.000s 
CMD_DO_01,  DA_DO_01,  0,  RDBC,  BCU_1,  DO,  1,  Present_Value,  30.000s 
CMD_DO_02,  DA_DO_01,  1,  RDBC,  BCU_1,  DO,  2,  Present_Value,  30.000s 
CMD_DO_03,  DA_DO_01,  2,  RDBC,  BCU_1,  DO,  3,  Present_Value,  30.000s 