Technologies Computer Driver Instruction Manual
FS-8700-16 BACnet PTP Serial Driver Manual        Page 5 of 20 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970  email: support@fieldserver.com 
4.  Configuring the FieldServer as a BACnet Client 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Instruction Manual. 
The  information  that  follows  describes  how  to  expand  upon  the  factory  defaults  provided  in  the 
configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer). 
This section documents and describes the parameters necessary for configuring the FieldServer to 
communicate with a BACnet Server. 
4.1.  Data Arrays/ Descriptors 
The  configuration  file  tells  the  FieldServer  about  its  interfaces,  and  the  routing  of  data  required.  In 
order  to  enable  the  FieldServer  for  BACnet  communications,  the  driver  independent FieldServer 
buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be 
declared  in  the  “Client  Side  Nodes”  section,  and  the  data  required  from  the  servers  needs  to  be 
mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default. 
Section Title 
Data_Arrays 
Column Title  Function  Legal Values 
Data_Array_Name  Provide name for Data Array 
Up  to  15  alphanumeric 
characters 
Data_Format  Provides data format 
Float, Bit, Uint16, Uint32, 
Sint16, Sint32, Packed_Bit, 
Byte, Packed_Byte, 
Swapped_Byte 
Data_Array_Length  Number of Data Objects  1-10,000 
Example 
// Data Arrays     
Data_Arrays     
Data_Array_Name,  Data_Format,  Data_Array_Length 
DA_AI_01,  Float,  200 
DA_AO_01,  Float,  200 
DA_DI_01,  Bit,  200 
DA_DO_01,  Bit,  200 
4.2.  Setting the FieldServer Node_ID and Network Number 
Section Title 
FieldServer 
Column Title  Function  Legal Values 
System_Node_ID  Configure Node_ID of FieldServer  1-255 
Network_Number  BACnet Network Number 
1-65535, 5 