FS-8700-15 Modbus Daniels Manual            Page 6 of 7 
4.4.4.  Map Descriptor Example. 
Section Title 
Map Descriptors 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  Address,  Length,  Scan_Interval 
CMD_AI,  DA_AI,  0,  RDBC,  PLC 1,  30000,  20,  1s 
The remote 
Modbus Daniels 
device is 
specified here 
with the node 
name previously 
declared under 
the nodes 
section. 
The data array 
where the read 
data will be 
stored is 
specified here. 
This data array 
and its format 
must be 
specified under 
the data arrays 
section. 
Note the use of 
the RDBC 
function here 
which will 
cause this map 
descriptor to 
continuously 
read data every 
scan interval 
from the 
remote device.