User Guide
FS-8700-15 Modbus Daniels Manual            Page 5 of 7 
4.4.  Client Side Map Descriptors 
4.4.1. FieldServer Related Map Descriptor Parameters 
Section Title 
Map Descriptors 
Column Title  Function  Legal Values 
Map_Descriptor_Name 
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array 
where data is to be 
stored in the 
FieldServer 
One of the Data Array 
names from “Data Array” 
section above 
Data_Array_Offset 
Starting location in 
Data Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
RDBC, WRBC, WRBX 
4.4.2.  Driver Related Map Descriptor Parameters 
Section Title 
Map Descriptors 
Column Title  Function  Legal Values 
Node_Name 
Name of Node to fetch 
data from 
One of the node names 
specified in “Client Node 
Descriptor” above 
Data_Type*  Data type  Register, Coil, AI, DI 
Length 
Length of Map 
Descriptor 
1-125 (Register, AI) 
1-800 (Coil, DI) 
Address 
Starting address of 
read block 
0000 – 6999 ( Coil ) 
7000 – 7999 ( Float ) 
10000 ( DI ) 
30000 ( AI ) 
40000 – 49999 ( Register) 
Data_Array_Low_Scale* 
Scaling zero in Data 
Array 
-32767 to 32767, default 0 
Data_Array_High_Scale* 
Scaling max in Data 
Array 
-32767 to 32767, default 
100 
Node_Low_Scale* 
Scaling zero in 
Connected Node 
-32767 to 32767, default 0 
Node_High_Scale* 
Scaling max in 
Connected Node 
-32767 to 32767, default 
100 
4.4.3. Timing Parameters 
Section Title 
Map Descriptors 
Column Title  Function  Legal Values 
Scan_Interval  Rate at which data is 
polled 
≥0.001s 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 