User Guide
FS-8700-15 Modbus Daniels Manual            Page 3 of 7 
factory defaults provided in the configuration files included with the FieldServer (See “.csv” 
sample files provided with the FS). 
This section documents and describes the parameters necessary for configuring the 
FieldServer to communicate with a Modbus Daniels Server. 
4.1. Data Arrays/Descriptors 
The configuration file tells the FieldServer about its interfaces, and the routing of data 
required. In order to enable the FieldServer for Modbus Daniels communications, the driver 
independent FieldServer buffers need to be declared in the “Data Arrays” section, the 
destination device addresses need to be declared in the “Client Side Nodes” section, and 
the data required from the servers needs to be mapped in the “Client Side Map Descriptors” 
section. Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the 
default. 
Section Title 
Data_Arrays 
Column Title  Function  Legal Values 
Data_Array_Name  Provide name for Data Array 
Up to 15 alphanumeric 
characters 
Data_Array_Format 
Provide data format. Each Data 
Array can only take on one 
format. 
Float, Bit, UInt16, 
SInt16, Packed_Bit, 
Byte, Packed_Byte, 
Swapped_Byte 
Data_Array_Length 
Number of Data Objects. Must be 
larger than the data storage area 
required by the Map Descriptors 
for the data being placed in this 
array. 
1-10,000 
Example
// Data Arrays     
Data_Arrays     
Data_Array_Name,  Data_Format,  Data_Array_Length, 
DA_AI_01,  UInt16,  200 
DA_AO_01,  UInt16,  200 
DA_DI_01,  Bit,  200 
DA_DO_01,  Bit,  200 
4.2.  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title  Function  Legal Values 
Port  Specify which port the  FS-X40 Serves: P1-P8, R1-R2 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 