User Guide
FS-8700-133 Genisys Manual                Page 6 of 13 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
4.2  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Port 
Specify which port the device is connected to the 
FieldServer 
P1-P8
1
Protocol 
Specify protocol used 
Genisys 
Baud* 
Specify baud rate 
300  ,600, 1200,  2400,  4800,  9600  (Vendor 
limitation) 
Parity* 
Specify parity 
None, Even, Odd (Vendor limitation) 
Data_Bits* 
Specify data bits 
8 (Vendor limitation) 
Stop_Bits* 
Specify stop bits 
1, 2 (Vendor limitation) 
Handshaking* 
Specify hardware handshaking 
None 
Poll_Delay* 
Time between internal polls 
0-32000 seconds, 0.05 seconds 
Example 
// 
// Client Side Connections 
// 
Connections 
Port 
,Baud 
,Data_Bits 
,Stop_Bits 
,Parity 
,Protocol 
P1 
,9600 
,8 
,1 
,None 
,Genisys 
1
 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for 
details of the ports available on specific hardware. 