4.2.  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title  Function  Legal Values 
Port  Specify which port the device is connected to the FieldServer  P1-P8
1
Protocol  Specify protocol used  FCI_E3 
Baud* 
Specify baud rate 
Vendor documentation indicated that the only supported Baud 
rate  was  9600. During  testing  we  learned  this  was  not  true.  The 
driver  was  tested  at  57600  and  9600  baud.  Testing  at  115200 
Baud produced intermittent result and should not be used. 
9600,  57600 
(Vendor 
Limitation) 
Parity*  Specify parity 
None  – 
(Vendor 
Limitation) 
Data_Bits*  Specify data bits 
8  (Vendor 
Limitation) 
Stop_Bits*  Specify stop bits 
1  (Vendor 
Limitation) 
Handshaking*
The E3 series panels do not support hand shaking. 
Example 
// Client Side Connections 
Connections 
Port,  Protocol,  Baud,  Parity 
P1,  FCI_E3,  9600,  None 