User Guide
FS-8700-132 Gamewell FCI-E3 Driver Manual            Page 3 of 20 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
1.   Gamewell FCI-E3 Series Serial Driver Description 
The Gamewell FCI-E3 Series System Control Units are manufactured by Fire Control Instruments. An E3 
Panel  with an enabled  serial port  can  transmit  data  to  a  FieldServer  which  can,  in  turn, make  the  data 
available to other devices including those which communicate using different protocols (e.g. BACnet) 
This passive Client driver does not poll for data, nor does it send data or commands to the E3. Messages 
received  from  the  E3  are  analyzed  and  are  then  either  discarded  or  used  to  update  the  FieldServer’s 
internal  Data  Arrays.  The  action  depends  on  which  types  of  events,  the  type  of  device  generating  the 
event  and  device  address  the  FieldServer  has  been  configured  to  process.    Once  stored  in  the 
FieldServer the data is available to be read or written using other protocols such as BACnet. 
No  automatic  panel  data  synchronization  technique  exists.  The  data  in  the  FieldServer  and  the  panel 
status have to be synchronized manually. This typically requires a panel reset. 
Since the driver cannot send data or commands to the E3 it cannot be used to acknowledge, silence or 
reset alarms and other events. 
The driver  can  process  messages from  networked panels.  The  driver  connects  to  the  main  panel. 
Subsidiary panels are configured to send event data to the main panel which then sends messages to the 
FieldServer. Node information  is sent in  the line preceding the event and the  driver uses this to 
determine the panel at which the event originated and to store data appropriately. 
The driver provides both Client and Server emulation.  The Server side of the driver is intended to support 
FieldServer’s Quality Assurance program and is not intended to provide complete emulation of an E3 and 
is  thus  not  fully  documented.    Should  you  require  the  Server  side  functionality  to  be  documented  and 
enhanced, please contact FieldServer’s sales group. 
Max Nodes Supported 
FieldServer 
Mode 
Nodes
Comments 
Client  1 
1  Node  per  serial  port.    If  there  is  more  than  one  alarm  panel  they  can  be 
networked and configured to send event data to the primary panel. The driver 
can process messages which identify the node of origin. 
Server  N/A  Server side is not supported. See description. 