Message  Description 
FCI_E3:#17 Err. Loop=%d < 1. Rejected. , drv_bd->loop ) 
This  message  should  only  be  printed  if  a 
byte  in  a  message  has been  corrupted.  If 
you  notice  it  more  than  once  then  take  a 
log and contact tech support. 
FCI_E3:#18  Err.  Loop  Type='%c'(%#x)  Not  recognized.  , 
drv_bd->point_identifier[2] , drv_bd->point_identifier[2] ) 
If this error is repeated often it is possible 
that a FCI  firmware update  has made  the 
driver  unusable.  Take a  log  and  contact 
tech support. 
FCI_E3:#19 Err. Relay=%d < 1. Rejected. , drv_bd->relay 
FCI_E3:#20 Err. Zone=%d < 1. Rejected. , drv_bd->zone" 
This  message  should  only  be  printed  if  a 
byte  in  a  message  has been  corrupted.  If 
you  notice  it  more  than  once  then  take  a 
log and contact tech support. 
FCI_E3:#21 Err. Point Type not recognized 
FCI_E3:#22 Err. Undefined Point Type" 
Valid  Point  Types  are  listed  in  section 
4.4.2
5
FCI_E3:#23 Err. Event Type not recognized 
FCI_E3:#24 Err. Undefined Event Type 
Valid  Event  Types  are  listed  in  section 
4.4.2
5
FCI_E3:#25a Err. Address+Length>99. Length Truncated 
FCI_E3:#25b Err. Address+Length>99. Length Truncated 
The  maximum  value  for  a  sensor/module 
is  99.    The combination of  address  and 
length specified produce a number > 99
5
FCI_E3:#26 Err. Invalid Module number. Expected 1..99 
FCI_E3:#27a Err. Invalid Loop number. Expected 1..10 
FCI_E3:#27b Err. Invalid Loop number. Expected 1..10 
FCI_E3:#27c Err. Invalid Loop number. Expected 1..10 
FCI_E3:#28 Err. Invalid Sensor number. Expected 1..99 
FCI_E3:#29 Err. Invalid Zone number. Expected 1..255 
FCI_E3:#30 Err. Invalid Relay number. Expected 1..255 
Correct the configuration file
5
FCI_E3:#31 Err. Point Type Invalid. 
Valid  Point  Types  are  listed  in  Section 
4.4.2
5
FCI_E3:#32 Err. No MD Length. Default to 1 
The length of each Map Descriptor should 
be specified. Refer to Section 4.4.2
5
FCI_E3:#33 Err. Driver can’t poll or write. 
The  driver  can  only  listen  passively  for 
message from the panel. Map Descriptors 
may not be configured as active. 
5
FCI_E3:#36 Err. Too Short. Bytes=%d , conn->ux_iptr" 
An  event  message  is  less  than  80  bytes 
long. If this error is repeated often it is 
possible  that  a  FCI  firmware  update  has 
made the driver unusable. Take a log and 
contact tech support. 
5
Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to 
take effect.