User Guide
FS-8700-132 Gamewell FCI-E3 Driver Manual            Page 17 of 20 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
Appendix B.  Driver Error Messages. 
Message  Description 
FCI_E3:#1  FYI.  Use  a  DA  called  <%s>  to  expose 
diagnostic info., FCI_E3_STATS_DA ) 
Refer to Appendix B.1 
FCI_E3:#2  FYI.  Added  Event  Desc=<%s>  Index=%d 
Categ=%d  ,  new_event_desc  , 
new_event_desc_index_value , new_event_desc_categ ) ; 
Printed  for  information  only.  No  action 
required if it confirms your expectations. 
FCI_E3:#3  Err.  No  space.  Reject  Event  Desc=<%s> 
Index=%d  ,  new_event_desc  , 
new_event_desc_index_value ) ; 
There is only space for 60 event types.
4
FCI_E3:#4  FYI.  Duplicate  Event  Desc=<%s>.  , 
new_event_desc ) ; 
FCI_E3:#5  FYI.  Duplicate  Event  Desc=<%s>.  , 
new_event_desc ) ; 
The  Event  type  being  added  already 
exists.    If  you  are  updating  the  category, 
ignore the message. Otherwise correct the 
configuration file.
4
FCI_E3:#6  Err.  Event  Index=%d.  Too  big  to  set  bit., 
drv_bd->event_index ) 
If  the  event  index  is  greater  than  64  then 
the data cannot be stored as bits - only 64 
bits are reserved for events. 
FCI_E3:#7a  Err.  DA=%s  too  short.  Rqd=%d,  dt-
>buffer_name , offset ); 
FCI_E3:#7b Err. DA=%s too short. Rqd=%d, possible_md-
>data->buffer_name , offset ); 
The  MD  in  question  has  a  length  and 
offset  which  makes  it  run past  the end  of 
the  Data  Array.  Message  7b  is  printed 
when data is being stored as bits.
4
FCI_E3:#8  FYI.  Reset  was  rcvd  and  processed!  Stamped 
%s %s , drv_bd->time , drv_bd->date ) 
Printed  for  information  only.  No  action 
required. 
FCI_E3:#9 Err. Reset was ignored. 
A  reset  was  received  but  the driver could 
not  reset  any  data.    'Clear_on_Reset' 
possibly set to 'no' on all Map Descriptors?
FCI_E3:#10  FYI.  Reset  of  DA=%s  Off=%d  Len=%d, 
possible_md->data->buffer_name  ,  possible_md-
>bxi_data_buffer_offset , possible_md->data_length ); 
Printed  for  information  only.  No  action 
required. 
FCI_E3:#11  Err.  Cant  reset  DA=%s  len=%d  rqd=%d, 
possible_md->data->buffer_nam
e  , 
da_get_length_in_items ( (DAH_TYP) possible_md->data ) 
,  possible_md->data_length+possible_md-
>bxi_data_buffer_offset ); 
The  Map  Descriptor  in  question  has  a 
length  and  offset  which  makes  it run past 
the end of the Data Array.
4
FCI_E3:#12a Err. No MD's to store message data. 
FCI_E3:#12b Err. No MD's to store message data." 
FCI_E3:#13  Err.  Msg  was  ignored.  MD  Required  for 
Storage. 
The  Driver could  not  find  a  place to store 
data from a message received.  If the data 
is  not  required  then  the message  may be 
ignored.    Otherwise  update  the 
configuration file
4
.
FCI_E3:#13a Err. Diagnostic 1); 
FCI_E3:#13b Err. Diagnostic 2); 
FCI_E3:#13c Err. Diagnostic 3); 
Take  a  log.  Try and repeat  the  event that 
caused  the  message  to  be  printed.  Then 
contact tech support. 
FCI_E3:#14  Err.  <%s>  file  not  found.,  md-
>mapdesc_name ) ; 
FCI_E3:#15  Err.  Event  Type=<%s>  Not  recognized."  , 
drv_bd->event_desc ) 
FCI_E3:#16  Err.  Point  Type='%c'(%#x)  Not  recognized.  , 
drv_bd->point_identifier[0] , drv_bd->point_identifier[0] ) ; 
If this error is repeated often it is possible 
that a FCI  firmware update  has made  the 
driver  unusable.  Take a  log  and  contact 
tech support. 
4
Correct the configuration file, download to the FieldServer and restart the FieldServer for the changes to 
take effect.