User Guide
FS-8700-132 Gamewell FCI-E3 Driver Manual            Page 16 of 20 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
Appendix A.4.  Panel Synchronization 
Manual synchronization is required.  When the “Reset” button on the panel is pressed  a message is 
transmitted to the FieldServer, which clears the data in the FieldServer.  After a reset the panel sends 
messages to report all abnormal states. When all these messages have  been processed  the 
FieldServer and panel will be synchronized. This process can be repeated at any time. 
Appendix A.5.  What happens when the panel sends a Reset Message 
When a panel sends a reset message the driver processes  every single Map Descriptor, looking at 
the ‘Clear on Reset’ parameter (See section 4.4.2).  If the parameter is set to yes, then the driver sets 
all the Data Array elements referenced by the Map Descriptor to zero by looking up the Data Array 
Name, the Data Array offset and the length.  The  driver also clears the relevant sections  of  a  Data 
Array specified with the DA_Bit_Name parameter. 
The process can take some time.  For this reason, it is suggested that  you take care not to set the 
Map Descriptor length to a value larger than necessary. 
Appendix A.5.1.  Networked Panels. 
The driver can processes messages and store data from multiple panels provided that: 
•  The  panels  are  connected  in  an  FCI  network  and  the  panels  are  configured  to  report  their 
events to the main panel 
•  The main panel is configured to send the Node of origin in a message preceding the event 
message. Consult with FCI for information on how to achieve this. 
Example of message sent by a panel that is networked.  The driver is dependent on seeing the 
node of event origin included in parenthesis before each event message. 
Node02: 
MISSING                    Acclimate    L1S041 00:17:06 
01/01/06 
Node55: 1st Floor Lobby 
DISCONNECT RSTRD                  Ion Detector   L1S024 09:51:44 
01/15/06 
Local: 
FIRST ALARM                     Photo Detector L1S001 09:24:52 
12/01/06 
The main panel is identified as ‘Local’. The driver interprets this as Node_ID=0. 
To capture events from multiple networked panels a Node Descriptor is required for each panel 
with the appropriate Node_ID. Each Node requires a set of Map Descriptors. 