FS-8700-132 Gamewell FCI-E3 Driver Manual            Page 10 of 20 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com 
4.5.  Map Descriptor Example 1 – Sensor / Module Events 
If messages from Loop 1, Module 1 to 99 are received then the Map Descriptor in this example will be used for storage. If modules occur on more 
than one loop, one Map Descriptor is required per loop. In this example the event type is set to ‘Alarm’ so only “Alarm” events will be stored.  The 
“Event_Type” can be changed to suit the required data. If all events are required, the parameter should be set to “Any”. 
Example: 
 F.S.E.C. :[CR][LF] 
 FIRST ALARM: UP STAIRS N. ENT Manual Station L1M21 00:37:28 01/01/99[CR][LF] 
// Client Side Map Descriptors 
Map_Descriptors                     
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name,  Event Type,  Point Type,  Relay/Loop/Zone Number,  Address,  Length,  Clear_on_Reset 
ModuleData1,  DA_MODULE,  0,  Passive_Client,  Panel-01,  Alarm,  Module,  1,  1,  99,  Yes 
Unique  Map 
Descriptor 
Names  are 
recommended. 
The  address 
specifies  the 
starting  Module 
number  and  the 
Length  tells  the 
driver  the  range 
of Modules. 
In this example: 
Module 1 to 99
Change  this  to 
‘Sensor’  for 
sensors. 
Only  Alarm 
events will be 
stored. 
The  Data  Array 
name  and 
starting  location 
that data should 
be stored. 
The  driver 
listens 
passively  for 
messages  from 
the  Panel.  It 
cannot  poll  for 
data. 
The  name  of 
the  Node 
defined  in  the 
Node 
Descriptor 