4.5.  Map Descriptor Example: Read Indications 
The  following  Map  Descriptors  will  read  256  indication  statuses  from  physical  Server  Node_A  (described  in  Client  Side  Node 
Descriptors section) after every 1 second. One such Map Descriptor is required for each Node. 
// Client Side Map Descriptors 
Map_Descriptors                 
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name  Data_Type,  SCS128_Poll_Type,  Length,  Scan_Interval 
CMD_DI1,  DA_DI,  0,  RDBC,  Node_A,  Flag,  Recall,  256,  1 
CMD_DI2,  DA_8I_01,  0,  RDBC,  Node_A,  Byte,  Poll,  32,  1 
CMD_DI3,  DA_16I_01,  0,  RDBC,  Node_A,  Register,  2,  16,  1 
CMD_DI4,  DA_32I_01,  0,  RDBC,  Node_A,  32-Bit_Reg,  1,  8,  1 
Name  of  one  of  the 
Data  Arraya  defined 
in  the  Data_Array 
section.  Indication 
statuses  will  be 
stored  in  this  Data 
Array 
Starting  offset 
in  Data  Array 
to  hold  1
st
indication 
status 
One  of  the  Nodes 
declared  in  Node 
Section.  Indications 
will be read from the 
station  address 
belonging  to  this 
Node 
Frequency  (in 
seconds)  to  read 
Indication Statuses 
Number  of  consecutive 
locations  in  the  Data 
array  to  be  used  for 
storing  data  from  the 
Server.