User Guide
FS-8700-128 Safetran SCS-128 Manual            Page 8 of 15 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com 
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com 
4.4.  Client Side Map Descriptors 
4.4.1.  FieldServer Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name
Name of this Map Descriptor 
Up  to  32  alphanumeric 
characters 
Data_Array_Name 
Name  of  Data  Array  where  data 
is to be stored in the FieldServer 
One  of  the  Data  Array  names 
from “Data Array” section above 
Data_Array_Offset  Starting location in Data Array 
0  to  maximum  specified  in  “Data 
Array” section above 
Function  Function of Client Map Descriptor  Rdbc, Wrbc, Wrbx 
4.4.2.  Driver Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name  Name of Node to fetch data from 
One  of  the  Node 
names  specified  in 
“Client  Node 
Descriptor” above 
SCS128_Poll_Type*
Specify Poll_type 
‘Recall’ or 2 always poll for current indications 
‘Poll’ or 1 request for indications if changed 
‘Controls’ or 3 writes controls to target device 
‘Cutoff’ or 5 or 6 send  ‘cutoff’ command to 
target device 
For  Read  Map 
Descriptors : 
Recall, 2, Poll, 1, 
For  Write  Map 
Descriptors : 
Controls, 3 
Cutoff, 5, 6 
Data_Type* 
‘Flag’ - each byte of Indication statuses will be 
stored  in  8  consecutive  locations  in  the  Data 
Array.  On  write;  one  Control  byte  will  be 
composed from 8 consecutive locations. 
‘Byte’- each byte of Indication statuses will be 
stored  as  an  8  Bit  Integer  at  the  specified 
location. On  Write;  one Control byte will be 
composed from a single location. 
‘Register’ - two bytes of Indication statuses will 
be  stored  as  a  16  Bit  integer  at  the  specified 
location.  On  Write;  two  Control  bytes  will  be 
composed from a single location. 
’32-Bit_Reg’  four  bytes  of  Indication  statuses 
will  be  stored  as  32  Bit  integers  at  the 
specified location. On Write, four Control bytes 
will be composed from a single location. 
Refer to Appendix A 
Flag, Byte, Register, 
32-Bit_Reg 
Length* 
Length of Map Descriptor 
Number  of  indications  to  store  or  number  of 
controls to write as per Data_Type. 
Flag: 8-256, 16 
Byte: 1-32, 2 
Register: 1-16, 1 
32-Bit_Reg: 1-8, 1 
4.4.3.  Timing Parameters 
Column Title  Function  Legal Values 
Scan_Interval  Rate at which data is polled  ≥0.001s 