5.3.  Server Side Map Descriptors 
5.3.1.  FieldServer Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name
Name of this Map Descriptor 
Up  to  32  alphanumeric 
characters 
Data_Array_Name 
Name  of  Data  Array  where  data  is  to  be 
stored in the FieldServer 
One  of  the  Data  Array 
names from “Data Array” 
section above 
Data_Array_Offset  Starting location in Data Array 
0 to  maximum specified 
in  “Data  Array”  section 
above 
Function  Function of Server Map Descriptor  Server 
Server_Hold_Timeout 
Specifies  time  FieldServer  will  reserve 
Server side  connection while  waiting for 
the  Client  side  to  update  data  in 
Data_Array (if necessary) 
>1.0s 
5.3.2.  Driver Specific Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name  Name of Node to fetch data from 
One  of  the  Node 
names  specified  in 
“Client  Node 
Descriptor” above 
SCS128_Poll_Type
Specify type of requests to handle from client. 
‘Indications’ Handle all read requests from client.
‘Controls’ Handle all write requests from client 
Indications, Controls 
Data_Type 
‘Flag’  each  byte  of  Controls  will  be  stored  in  8 
consecutive  locations  in  the  Data  Array. 
Similarly  while  responding  Indications;  status 
byte  will  be  composed  with  data  from  8 
consecutive locations. 
‘Byte’  each byte  of  Controls  will  be  stored  as  8 
Bit  Integer  at  specified  location.  Similarly  while 
responding  Indications;  status  byte  will  be 
composed with data from single location. 
‘Register’ every two  bytes of  Controls will be 
stored as 16 Bit  integer at specified location. 
Similarly  while  responding  indications;  two 
Control  bytes  will  be  composed  with  data  from 
single location. 
’32-Bit_Reg’  every  four  Control  bytes  will  be 
stored as 32 Bit  integer at specified location. 
Similarly  while  responding  indications;  four 
Control  bytes  will  be  composed  with  data  from 
single location. 
Refer to Appendix A 
Flag, Byte, Register, 
32-Bit_Reg 
Length 
Length of Map Descriptor 
Number of indications to  serve  or  number of 
controls to store as per Data_Type. 
Flag: 8-256, 16 
Byte: 1-32, 2 
Register: 1-16, 1 
32-Bit_Reg: 1-8, 1 
Address  Irrelevant parameter for this driver   