4.6.  Map Descriptor Example: Write Controls 
The following Map Descriptor will write 256 controls to physical Server Node_A (described in Client Side Node Descriptors section) 
whenever any of the control statuses changes/updates. One such Map Descriptor is required per Node. 
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_name  Data_Type  Length  SCS128_Poll_Type 
CMD_DO1,  DA_DO_01,  0,  Wrbx,  Node_A,  Flag,  256,  Controls 
CMD_DO2,  DA_8O_01,  0,  Wrbx,  Node_A,  Byte,  32,  Controls 
CMD_DO3,  DA_16O_01,  0,  Wrbx,  Node_A,  Register,  16,  Controls 
CMD_DO4,  DA_32O_01,  0,  Wrbx,  Node_A,  32-Bit_Reg,  8,  Controls 
Name  of  one of 
the Data Arrays 
defined  in 
Data_Array 
section.  This 
Data  Array 
holds  control 
statuses  to  be 
written to other 
devices. 
Starting  offset 
in  the  Data 
Array  which 
holds  the  1
st
control status. 
One  of  the 
Nodes declared 
in  the  Node 
Section. 
Indications  will 
read  from  the 
station  address 
belonging  to 
this Node 
Number  of 
consecutive  locations 
in  the  Data  array  to 
use when issuing the 
Write command. 
Wrbx:  send  write 
command  to  the  Server 
when  the  associated 
Controls  updates  or 
changes. 
To  write  continuously  use 
Wrbc  as  function  and  add 
a Scan_Interval parameter 
to configure  how often to 
write. 