FS-8700-123 MetOne Particle Counter Serial Driver Manual      Page 8 of 26 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@fieldServer.com 
4.2.  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title  Function  Legal Values 
Port 
Specify  which  port  the  device 
is  connected  to  the 
FieldServer 
P1-P8, R1-R2
1
Protocol  Specify protocol used  MetOne 
Baud*  Specify baud rate 
9600 (Vendor limitation). 
Parity*  Specify parity 
None (Vendor limitation) 
Data_Bits*  Specify data bits 
8 (Vendor limitation) 
Stop_Bits*  Specify stop bits 
1 (Vendor limitation) 
Handshaking* 
Specify  hardware 
handshaking 
RTS, RTS/CTS, None 
Poll_Delay*  Time between internal polls 
0-32000 seconds, 0.05 seconds 
Example 
// Client Side Connections 
Connections 
Port,  Protocol,  Baud,  Parity,  Handshaking,  Poll_Delay 
P8,  MetOne,  9600,  None,   None,  0.100s 
4.3.  Client Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node  Up to 32 alphanumeric characters 
Node_ID  The ‘Device’ Number  1-64 
Protocol  Specify protocol used  MetOne. 
Connection 
Specify which port  the device is 
connected to the FieldServer 
P1-P8, R1-R2
1
PLC_Type 
Identifies  for  the  driver  the  family 
of  Particle  Counters/Manifolds 
connected to. 
“237 Family” 
“2408” or “Manifold” 
“4800” 
“HF CNC” 
Example 
Nodes         
Node_Name,  Node_ID,  Protocol,  PLC_Type,  Connection 
PLC 1,  1,  MetOne,  237 Family,  P8 
1
Not  all  ports  shown  are  necessarily  supported  by  the  hardware.  Consult  the  appropriate  Instruction 
manual for details of the ports available on specific hardware.