User Guide
FS-8700-123_MetOne Particle Counter by Hach Ultra Analytics Manual  Page 22 of 26 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@fieldServer.com 
Message  Description 
MET1:#07 Err. Cant  find DA=%s 
to get Mode. 
MET1:#07b  Err.  Cant find DA=%s 
to set Mode. 
MET1:#07c  Err.  Cant  find  DA=%s 
to get current record. 
MET1:#07d  Err.  Cant find DA=%s 
to store times. 
Printed  by the  Server  side  of  the  driver.  The  Server  cant 
find the specified DA which will be used to store incoming 
data  or  from  which  data  will  be  extracted  to  form  a 
response.
3
MET1:#08a  Err.  Invalid  time 
string=%s 
MET1:#08b  Err.  Invalid  time 
string=%s 
Printed by the Server side of the driver. See notes for #4. 
MET1:#09a  Err. 
Met1_Function=%d  is  unknown. 
MD=%s 
The  reported  MD  has  a  Met1  function  not  recognized  by 
the driver. This should never happen. Take a log and send 
a copy of the log and your configuration to Tech Support. 
The FieldServer web site provide tools and instructions for 
taking logs 
Met1:#10 FYI. No place  to store 
label data. Label=%s MD=%s 
This messages is printed a maximum of 15 times and then 
suppressed. 
Where the label method is being used to store data. (See 
section 4.13) then this message is printed if the driver can’t 
find  an  Map  Descriptor  with  a label which  matches  the 
reported label found in the message from the field device. 
The message is printed simply to alert users to what count 
labels  are  being  returned.    Passive  Map  Descriptors  can 
be created to  store the  reported data, or  the message 
could be ignored. 
MET1:#11a Err. Diagnostic 6 
MET1:#11b Err. Diagnostic 1 
MET1:#11c Err. Diagnostic 4 
MET1:#11d Err. Diagnostic 2 
MET1:#11e Err. Diagnostic 7 
Printed by the Server side of the driver. These are printed 
when internal diagnostics are triggered. This should never 
be the case in  an operational system.  Take a  log and 
contact  Tech  Support.  The  FieldServer  web  site  provide 
tools and instructions for taking logs 
MET1:#12  FYI.  Use  an  Array 
called  <%s>  to  expose  diagnostic 
info. 
This message can be ignored. For more information read 
Appendix A.2 
3
Update the configuration file, download the modified configuration file and reset the FieldServer for the 
changes to take effect.