User Guide
FS-8700-123_MetOne Particle Counter by Hach Ultra Analytics Manual  Page 21 of 26 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com 
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@fieldServer.com 
Appendix A. Driver Error Messages 
Message  Description 
MET1:#01  Err.  Cant  set  mode  to 
state=%d for MD=%s 
An attempt was made to send a mode control command to 
a device. The required mode is derived from the Data 
Array  value.  This  message  is  printed  when  the  driver 
doesn’t  recognize  the  value  found  and  thus  cannot  send 
the  command.    This  can  be  resolved  by  having  the 
upstream  device  send  a  valid  value  to  the  DA:offset 
associated with the reported MD.  Refer to the example in 
section 4.9 for more information. 
MET1:#02  Err.  Cant  set  Sample 
time to zero. MD=%s 
The reported Map Descriptor is being used to send a new 
Sample Time to  the field device but the  time found in the 
Data Aarray:offset specified on the Map Descriptor is zero. 
The driver cannot send a sample time of zero. This can be 
resolved by by having the upstream/other protocol send a 
non-zero value to the DA:Offset. 
MET1:#03  Err.  Cant  set  Holde 
time to zero. MD=%s 
The reported Map Descriptor is being used to send a new 
Hold Time to the field device but the time found in the Data 
Array:offset  specified  on  the  Map  Descriptor  is  zero.  The 
driver  cannot  send  a  sample  time  of  zero.  This  can  be 
resolved by by having the upstream/other protocol send a 
non-zero value to the DA:Offset. 
MET1:#04a/b  Err.  Invalid  time 
string=%s MD=%s 
Message  4a  is  printed  when  a  response  to  a  poll  for  the 
Sample/Hold time returned a response whose time cannot 
be correctly understood by the  driver.    If this error occurs 
rarely  it  may  be  a  consequence  of  an  occasional 
corruption.  If it occurs consistently, take a log, ensure this 
event occurs at least once during the log and contact Tech 
Support.  The  FieldServer  web  site  provide  tools  and 
instructions for taking logs. 
Message 4b is printed when the time is formatted correctly 
but found be  an invalid time. The same considerations 
apply as with 4a. 
MET1:#05  FYI.  MD=%s  too  short 
to  store  all.  Ignored  stat 
incremented  each  time  this 
happens.  Play  safe  -  set  MD 
length=20. 
This message is printed once and trhen suppressed. 
The  Map  descriptor  is  not  long  enough  to  store  all  data 
from the record..
2
 Refer to section 4.11. 
MET1:#06  Err.  Cant  store  Current 
Record. Chksum err. 
If  a  response  to  a  read  Current  Record  contains  a 
checksum error the driver prints this message. 
If this error occurs rarely then it may be a consequence of 
an  occasional  corruption.  If  it  occurs  consistently,  take  a 
log, ensure this event occurs at  least  once  during the log 
and  contact  Tech  Support.  The  FieldServer  web  site 
provide tools and instructions for taking logs 
2
Update the configuration file, download the modified configuration file and reset the FieldServer for the 
changes to take effect.