4.11.  Map Descriptor Example 7 – Read the Current Record 
In this example the driver reads the current record and stores the values in the specified Data Array.  A single record comprises the 
following data: status; date and time and a count for 1 or more locations.  The driver has no advance knowledge of the number of 
count fields to expect in the response.  It simply stores them in consecutive locations in the Data Arrays. To map these counts to an 
upstream  protocol,  the  order  of  the  count  fields  must  be  known.    The  driver  can  store  a  maximum  of  20  count  fields.    The  Map 
Descriptor length must be set to a value that allows for enough data to be stored bearing in mind that it requires 8 DA elements to 
store the status, date and time and period. 
One of these Map Descriptors is required for each device from which the current record is to be read.. 
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name  Met1_Function,  Length,  Scan_Interval 
Read Record,  DA_DATA,  0,  Rdbc,  MET1,  Current Record,  20,  1.0s 
The  length  must  be set  to  a 
value  large  enough  to  store 
the 8 fixed  data items  and 
the variable number of count 
fields. 
Driver  stores  the  current  record  information  in  the  Data  Array 
specified  here,  starting  at  the  specified  offset.  The  data  is 
arranged as follows. 
0
Status Byte 
1
Date - Month 
2
Date - Day 
3
Date - Year 
4
Time - Hours 
5
Time - Minutes 
6
Time - Seconds
7
Period 
8
Count #1 
9
Count #2 
10
Count #3 … 