4.9.  Map Descriptor Example 5 – Change Mode 
In this example the driver sends a command to change the mode of the field device. The command sent is determined by the value 
found in the specified Data Array location. In this example the function is set to wrbx. This means the command message will be sent 
each time the value found at the specified offset in the specified Data Array is updated even if it is not changed 
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name  Met1_Function,  Length,   
Write_Mode,  DA_MODE_CTRL,  0,  wrbx,  MET1,  Mode ,  1,   
Set  length  to  1  for 
this Met1_Function 
Driver extracts one single value from this DA:Offset and uses 
the value to send a command to change the mode. 
Auto Sample Mode: Value=1 
Manual Sample Mode: Value=2 
Active Mode : Value = 3 
Standby Mode: Value = 4 
If the value found is not valid then no 
command is sent.