4.8.  Map Descriptor Example 4 – Start / Stop Counting. 
In this example the driver sends a command to start or stop the field device from counting based on the value found in the Data Array 
element.  If the value is non-zero, the field device will be commanded to start counting.  If the value is zero, the field device will be 
commanded to stop counting. In this example the function is set to wrbx which means the command message will be sent each time 
the value found at the specified offset in the specified Data Array is updated even if it is not changed. 
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name  Met1_Function,  Length,  Scan_Interval 
Write_Count_Mode,  DA_COUNT_CTRL,  0,  wrbx,  MET1,  Count ,  1,  1.0s 
When the function is 
wrbx then  the scan 
interval  parameter  is 
ignored. 
Set  length  to  1  for 
this Met1_Function
Command  is  sent 
each  time  the  value 
at  DA:offset  is 
updated. 
Driver  extracts  one  single  value  from  this 
DA:Offset  and  uses  the  value  to  send  a 
command to start counting (non-zero value) or 
stop counting (zero value) 