4.6.  Map Descriptor Example 2 – Write Hold (or Sample) Times to a Device. 
In this example the driver writes the hold time to the field device.  The time is specified in seconds.  A max of 23 hours 59 minutes 
and 59 seconds can be specified.  To write Sample Times simply change the Met1_Function to ‘Sample Time.  The driver extracts 
the time from the response and stores the hours at the specified offset, the minutes in the next Data Array location and the seconds 
in the 3
rd
 location. 
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name  Met1_Function,  Length   
Write_Time,  DA_TIMES,  0,  WRBX,  MET1,  Hold Time ,  1   
4.7.  Map Descriptor Example 3 – Read the operating mode. 
In this example the driver reads the operating mode from the field device. The driver stores a single element of data extracted from 
the  response.  The  driver  stores a  ‘C’  to  indicate  the field device  is  counting,  a  ‘H’  to  indicate the  device  is  holding  and  an  ‘S’  to 
indicate that  it has  stopped. If the mode is not recognized the  driver store  s  a ‘?’.  If another protocol reads these  states from the 
FieldServer it will probably display the ASCII value corresponding to each mode letter: ‘C’=67 ‘H’=72 and ‘S’=83 
// Client Side Map Descriptors 
Map_Descriptors               
Map_Descriptor_Name,  Data_Array_Name,  Data_Array_Offset,  Function,  Node_Name  Met1_Function,  Length,  Scan_Interval 
Write_Time,  DA_MODE,  0,  rdbc,  MET1,  Mode ,  1,  1.0s 
The driver will extract  the  time in 
seconds  from  the  Data  Array 
specified  here  and  use  it to  form 
the  command  message  to  the 
field device. 
The  location  in 
the Data Array 
This  function  ‘wrbx’  tells 
the driver to only send the 
command  each  time  the 
value  found  in  the 
specified  DA:offset  is 
updated.  Update  means 
each  time  some  other 
protocol  writes  to  this 
DA:offset 
Change  this  to 
‘Sample  Time’  to 
command a sample 
time  or  make  two 
Map  Descriptors  – 
each with the correct 
time function. 
Tells  the 
FieldServer  that 
one  element  of 
the data  array is 
reserved  for  this 
Map Descriptor. 