4.5.  Client Side Map Descriptors 
4.5.1. FieldServer Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Map_Descriptor_Name 
Name of this Map 
Descriptor 
Up to 32 alphanumeric 
characters 
Data_Array_Name 
Name of Data Array 
where data is to be 
stored in the 
FieldServer 
One of the Data Array 
names from “Data Array” 
section above 
Data_Array_Offset 
Starting location in Data 
Array 
0 to maximum specified in 
“Data Array” section above 
Function 
Function of Client Map 
Descriptor 
RDBC, WRBC 
4.5.2.  Driver Related Map Descriptor Parameters 
Column Title  Function  Legal Values 
Node_Name 
Name of Node to fetch 
data from 
One of the node names 
specified in “Client Node 
Descriptor” above 
Profibus_Data_Type  Arrangement of buffer data 
BYTE, WORD, BOOL, 
FLOAT 
Address 
Starting address of buffer 
in bytes 
0 - 243 
Length  Length of Map Descriptor 
1 - 244 ( BYTE ) 
1 - 122 ( WORD ) 
1 - 1952 ( BOOL ) 
1 - 61 ( FLOAT ) 
Important Note:
A maximum combined total length of 1536 bytes are permitted for all Map Descriptors 
accessing Slave devices. 
4.5.3. Timing Parameters 
Column Title  Function 
Legal 
Values 
Scan_Interval 
Rate at which data is transferred from FieldServer data 
arrays to Profibus Master buffers. 
≥0.001s 