User Guide
FS-8700-122 X30 Profibus DP Master Manual          Page 7 of 16 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Example 
// Data Arrays     
Data_Arrays     
Data_Array_Name,  Data_Array_Format,  Data_Array_Length 
Byte_Output,  Byte,  10 
Byte_Input,  Byte,  10 
Word_Output,  Uint16,  10 
Word_Input,  Uint16,  10 
Float_Output,  Float,  10 
Float_Input,  Float,  10 
4.3.  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title  Function  Legal Values 
Adapter Adapter Name  Prof_DP 
Example
// Client Side Connections 
Connections 
Adapter   
Prof_DP   
4.4.  Client Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node  Up to 32 alphanumeric characters 
Node_ID 
Station address of physical 
remote Profibus Slave 
0-125 
Protocol  Specify protocol used  Anybus_Prof_DP_M 
Example
// Client Side Nodes 
Nodes       
Node_Name,  Node_ID,  Protocol   
PDP_SLV003,  3,  Anybus_Prof_DP_M   
PDP_SLV125,  125,  Anybus_Prof_DP_M   