FS-8700-122 X30 Profibus DP Master Manual          Page 13 of 16 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
7) Select the first slave device, right-click on the Slot 1 line and choose Module selection. 
Now you have to add I/O modules up to the total number of bytes or words that will be 
transferred with this slave as set up in the config.csv file. For Example, for the Map 
Descriptor for Slave1 using 50 Words In and Out, you would choose the following 
modules: 
8)  Continue selecting other Slaves and adding modules for them as well. 
Important Note: Changing of Input and Output Addresses are not allowed. All addresses  
must be contiguous for the X30 Profibus to work correctly. 
9)  Select Online-> Driver selection and on the serial Tab, choose the serial port on the PC 
connected to the X30 by clicking on Configure-> Configure path. 
10) Make sure the X30 FieldServer is running and you’ve downloaded a matching 
configuration file to it with Node and Map Descriptors for each slave you have just 
configured Make sure you can connect with Ruinet to the X30 and there are no 
configuration errors. 
11) Choose Online-> Download configuration to install the embedded database in the X30. 