4.4.3.  Map Descriptor Example. 
// Client side Map Descriptors 
Map_Descriptors 
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,  Function,
Node_Name,
DeviceNet_Data_Type,
Address,
Length,
Scan_Interval
Get_Data,  Input_Data,  0,  RDBC,  CN1,  WORD,  0,  10,  1s 
Put_Data,  Output_Data,  0.  WRBC,  CN1,  WORD,  0,  10,  1s 
Note  that  each  address 
refers  to  an  individual 
remote  input  and  output 
buffer.  Each  buffer  can 
contain up to 512 bytes. 
Read  function  map 
descriptor  gets data 
from  the  DeviceNet 
network and stores it 
in  the  Input_Data 
data array. 
Write function map 
descriptor  puts 
data  from  the 
Output_Data  data 
array  onto  the 
DeviceNet 
network. 