Technologies Computer Driver Instruction Manual
FS-8700-114 DeviceNet Master Manual            Page 5 of 15 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
3.  Hardware Connections 
The FieldServer is connected to the DeviceNet network as shown in the connection drawing below. 
Connector Pinouts 
Pin
Signal  Description  Wire color
1  V-  Negative supply voltage
black 
2  CAN_L  CAN_L Bus line  blue 
3  SHIELD
Cable Shield  (bare) 
4  CAN_H 
CAN_H Bus line  white 
5  V+  Positive Supply Voltage  red 
3.1.  Hardware Connection Tips / Hints 
Use  the  recommended  network  cable  and  terminators  as  specified  by  the  DeviceNet  network 
organization and/or the manufacturer of your network equipment. 
Terminate each end of the DeviceNet network with a 121 Ω resistor 
The bus interface shall be supplied with 24DC ± 10% on the Fieldbus connector 