Technologies Computer Driver Instruction Manual
FS-8700-114 DeviceNet Master Manual            Page 3 of 15 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com 
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970  email: support@fieldserver.com 
1.  X30 DeviceNet Master Description 
The X30 DeviceNet Master Adapter driver can be used to emulate a single Master Scanner station on a 
DeviceNet  network.    The  FieldServer  DeviceNet  adapter  is  implemented  as  an  ODVA  profile  12 
communications  adapter.    Standard  DeviceNet  Baudrates  of  125k,  250k  and  500kbit/s  are  supported. 
The DeviceNet Master Scanner can open IO connections of up to a total of 512 Bytes in each direction to 
DeviceNet Slaves. 
Max Nodes Supported 
FieldServer 
Mode 
Nodes
Comments 
Client  1  The FieldServer can only emulate one DeviceNet Master station 
Server  63 
The driver can communicate with up to 63 Slaves as long as the FieldServer 
point count license is not exceeded 