Appendix B.  Driver Notes 
Appendix B.1.  Setting the FieldServer’s DeviceNet MAC ID and Baudrate 
The  MAC  ID  and  Baudrate  can  be  set  in  the  FieldServer’s  CSV  file  using  the 
System_Station_Address and DNet_Master_Baudrate parameters or it can be set with DIP switches 
as depicted below. 
Note: 
The System_Station_Address  parameter  must be  removed from the  configuration file if  the  DIP 
switch setting is to be used. 
If System_Station_Address has not been defined in the CSV file, the DIP switch value for both MacID 
and Baudrate will be used and the baud parameter in the CSV file will be ignored. 
Appendix B.2.  Using the Command and Status Data Arrays 
The Command Data Array controls the Scanner’s mode which can be either Run or Idle. The Scanner 
can  only be  configured  when  in Idle  mode.    A non-zero  value  at offset  zero in  the  Command  Data 
Array  will place  the Scanner  in Run  mode;  a value  of  zero will  place it  in Idle mode.   The  Scanner 