1.   Profibus X30 DP Slave Description 
The FieldServer Profibus DP Slave driver can  be used  to emulate a single Slave station  on a 
Profibus network. DP Masters can open a connection of up to 244 Bytes of Input and 244 Bytes 
of  Output  data,  but  not  exceeding  a  combined  total  of  416  Bytes  to  the  FieldServer.    The 
FieldServer can be added to the Profibus network with the use of the supplied GSD file for the 
ANYBUS card. Connection to the Profibus network is via a DB9 port on the ANYBUS card. 
Max Nodes Supported
FieldServer Mode  Nodes  Comments 
Server  1 
The  FieldServer  can  only  emulate  one  Profibus  DP  Slave 
station 