Technologies Computer Driver Instruction Manual
FS-8700-112 FCI 7100 Series Driver Manual          Page 9 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.3.  Client Side Node Descriptors 
Section Title 
Nodes 
Column Title  Function  Legal Values 
Node_Name  Provide name for node  Up to 32 alphanumeric characters 
Node_ID 
This parameter only has meaning 
for this driver when multiple 
panels are networked in an FCI 
network. In this case the 
NODE_ID is the panel number. 
Set the Node_ID of the local panel 
to zero, and create one node 
descriptor for each panel setting 
the Node_ID to the panel number. 
The protocol is node-less - the 
messages do not contain 
information identifying a unique 
source and/or destination node 
address. Thus this parameter need 
not be specified if only one 7100 is 
connected per FieldServer serial 
port. In networked configurations,  
specify whole numbers 0,1,2,3 … 
Protocol  Specify protocol used 
FCI_7100, FCI_7100_series, 
FCI7100 
FCI_Reset_Acti
on_Option* 
Only required for networked 
configurations. 
This parameter tells the driver 
what to do with ‘Reset’ messages. 
When not specified or set to 
‘Reset_by_any_Node ‘ then the 
driver will reset the data array 
points associated with the given 
node irrespective of the reset 
message’s origin. 
When set to 
‘Reset_by_this_Node_Only’ then 
the driver only resets the data 
associated with the given node if 
the reset originated from the same 
node. 
Reset_by_any_Node, 
Reset_by_this_Node_Only 
Connection 
Specify which port the device is 
connected to the FieldServer 
P1-P8, R1-R2
1
Example
// Client Side Nodes 
Nodes       
Node_Name,  Protocol,  Connection   
Panel-01,  FCI_7100,  P8   