Technologies Computer Driver Instruction Manual
FS-8700-112 FCI 7100 Series Driver Manual          Page 8 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
4.2.  Client Side Connection Descriptions 
Section Title 
Connections 
Column Title  Function  Legal Values 
Port 
Specify which port the device is 
connected to the FieldServer 
P1-P8, R1-R2
1
Protocol  Specify protocol used 
FCI_7100, FCI_7100_series, 
FCI7100 
Baud*  Specify baud rate  1200 – Vendor Limitation 
Parity* Specify parity  None – Vendor Limitation. 
Data_Bits*  Specify data bits  8 – Vendor Limitation 
Stop_Bits*  Specify stop bits  1 – Vendor Limitation 
Handshaking*  The 7100 series panels do not support hand shaking. 
Poll _Delay*  This commonly used parameter has no meaning for this driver. 
Example
// Client Side Connections 
Connections 
Port,  Protocol,  Baud,  Parity     
P8,  FCI_7100,  1200  None     
1
  Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction 
manual for details of the ports available on specific hardware.