Technologies Computer Driver Instruction Manual
FS-8700-112 FCI 7100 Series Driver Manual          Page 22 of 24 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com 
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com 
Appendix B.1.  Driver Stats Exposed. 
In addition to the standard FieldServer operating statistics the driver exposes certain key 
stats in a Data Array if required. An upstream device can then monitor these stats. 
Add the following to your configuration file to activate these stats. 
// Expose Driver Operating Stats. 
Data_Arrays     
Data_Array_Name,  Data_Format,  Data_Array_Length 
fci-7100-stats,  UINT32,  200 
The driver exposes stats based on a port handle. The offset specified in the table below 
must be added to the handle number multiplied by 100. i.e. for port whose handle is 1 then 
the driver will store the 1
st
 stat at 1+100*1=101. 
Stat  Offset Description 
#define FCI_7100_STAT_NO_PLACE_TO_STORE  1 
Increments each time point data 
is received but there is no Map 
Descriptor to store the data 
(any) 
#define 
FCI_7100_STAT_NO_PLACE_TO_STORE_ZONE 
2 
Increments each time point data 
is received but there is no Map 
Descriptor to store Zone data 
#define 
FCI_7100_STAT_NO_PLACE_TO_STORE_RELAY 
3 
Increments each time point data 
is received but there is no Map 
Descriptor to store Relay data 
#define 
FCI_7100_STAT_NO_PLACE_TO_STORE_LOOP 
4 
Increments each time point data 
is received but there is no MD to 
store the Loop data 
#define 
FCI_7100_STAT_NO_PLACE_TO_STORE_SENSOR 
5 
Increments each time point data 
is received but there is no MD to 
store the Sensor data 
#define 
FCI_7100_STAT_NO_PLACE_TO_STORE_MODULE 
6 
Increments each time point data 
is received but there is no MD to 
store the Module data 
#define FCI_7100_STAT_EMPTY_MSG  7 
Number of times that a message 
line was was zero bytes long 
(excluding the terminator) 
#define FCI_7100_STAT_SHORT_MSG  8 
Number of times that a message 
line was was too short probably 
a system id tag line 
#define FCI_7100_STAT_NO_RESET  9 
Increments each time a reset 
was rcvd but no DA was reset 
#define 
FCI_7100_STAT_NO_PLACE_TO_STORE_PANEL 
10 
Increments each time point data 
is received but there is no MD to 
store data that cannot be 
attributed to a zone, relay, loop, 
sensor, module 
#define FCI_7100_STAT_RCVD_MSGS  11 
Increments each time a 
message is received 